9 PIN D-SUB FEMALE
9 PIN D-SUB FEMALE at the UPS


Pin Name Dir Description
1 Battery Mode out This pin is shorted to PIN 5 (ground) if the mains power supply fails or is out of tolerance. (NORMALLY OPEN)
2 - - -
3 - - -
4 - - -
5 Ground - Ground terminal and common root of contacts at PIN 1, 8 and 9
6 - - -
7 UPS shut-down IN If a positive signal level (+5V to +12V DC) is applied, the UPS system switches off (PIN 5 is ground)
8 Battery Capacity Low OUT This pin is shorted to PIN 5 (ground) if the batteries have been discharged to such an extent that the remaining stored energy time is less than 2 minutes. (NORMALLY OPEN)
9 Battery Mode OUT The connection between this pin and PIN 5 (ground) is disconnected if the main power supply fails oe is out of tolerance. (NORMALLY CLOSED)

Notes

  • Direction is relative to UPS


References



edit tip iconSomething left uncovered? You are welcome to add information, explanations and fix errors, simply by clicking the edit link that appears on top of this page. There is no need to worry about accidentally damaging AllPinouts when adding or improving information, as other editors are always around to advise or correct obvious errors, and AllPinouts's software, known as MediaWiki, is carefully designed to allow easy reversal of editorial mistakes.